MC2000
Simplification
MC2000 overall system standard modular structure design, each sub-module is highly versatile. The sub-modules of MC2000 are prefabricated by factory and can be assembled on site, which has low requirement for installation place. The equipment can be put into use immediately after the arrival. In the process of utilization, it only needs one monitoring and management system during use with no need of facing multiple interfaces.
High efficiency
MC2000 has three types of aisle containment: hot-cold aisle containment (recommended), cold aisle containment and natural cooling. Thereinto, cold aisle containment can significantly improve the utilization of refrigerating capacity, hot aisle containment can improve the refrigerating efficiency of air conditioner, hot-cold aisle containment can improve the utilization of refrigerating capacity as well as the refrigerating efficiency of air conditioner. Its PUE (Power Usage Effectiveness) is industry-leading.
Flexibility
Overall system standard modular structure design, each sub-module is highly versatile. Multiple solutions can be implemented by combining them as needed.
The later stage can realize expansion easily.
Rack-mounted or row-mounted air conditioners can be installed.
It can be powered by either lead-acid or lithium batteries.
It supports single or dual power supply.
Reliability
The hot and cold aisles are fully enclosed and self-contained, adapting to various environments.
Overall system standard modular structure design can avoid system design problems.
System fault-tolerant design helps high reliability.
Strong and weak current separation design can make less electromagnetic interference.
Pass 8, 9 intensity electrified seismic performance test
Intelligence
MC2000 has built-in monitoring and management system and is configured with 10.1-inch industrial touch screen that can be used not only to view the parameters of the power supply and distribution, air conditioner, environmental variable and UPS but also to remotely monitor the operating parameters inside MC2000. Moreover, it can be connected to the superior monitoring platform via the internet for multi-network centralized monitoring and efficient management.
The MC2000 cabinet is equipped with intelligent LED ambient lights. When the temperature is 18-27°C, the light will be blue (normal work). When the temperature exceeds 27°C, the color of the light will gradually change from yellow to red (warning effect). When the front door is opened, the white light is on for operation and maintenance. At the same time, the LED ambient light is linked with the infrared sensor on the top of the cabinet. When the infrared sensor detects that a person is approaching the device, the smart LED ambient light starts up normally, and automatically turns off after 5 minutes away from the device.
Overall system parameters | Power mode | 380/400/415VAC, 50/60Hz, 3Ph+N+PE |
Aisle type | Cabinet type, single row aisle, hot-cold aisle containment | |
System protection grade | IP 50 (glass door) | |
Operating temperature | -20℃ ~ +45℃ | |
Number of IT cabinets | 1 - 12 | |
Max. power consumption of IT loads | 50kW | |
Max. power density per cabinet | 7kW | |
Installation | Concrete ground, raised flooring | |
Dimension | (600~7800)×1400×2000(W×D×H) (mm) | |
Refrigeration system | Input power supply | 220Vac; 380Vac |
Refrigerating capacity | Rack-mounted air conditioner: 3.5kW (5U) / 7.5kW (8U) / 12.5kW (10U) Row-mounted air conditioner: 25kW(300mm) | |
Air conditioner configuration | N, N+1 | |
Sensible heat factor (sensible cooling capacity / total cooling capacity) | 1 | |
Refrigerant | R410A | |
Air supply method | Supply air in front and return air in the rear | |
Installation | Rack-mounted, Row-mounted | |
Power supply and distribution system | Power input | Single-phase three-wire / Three-phase five-wire |
UPS capacity | 3kVA /6kVA /10kVA / 20kVA / 30kVA | |
UPS configuration | N, N+1, 2N | |
UPS rated input voltage | 220/230/240Vac single-phase, 380/400/415Vac three-phase | |
UPS input voltage range | 80 ~ 280Vac single-phase, 228 ~ 485Vac three-phase | |
UPS output power factor | 1 | |
UPS rated output voltage | 220/230/240Vac single-phase, 380/400/415Vac three-phase | |
UPS overall efficiency | ≥95% | |
Maintenance bypass | Support | |
Battery type | Lead-acid battery, lithium battery | |
Battery deployment | Battery pack, battery cabinet, battery rack | |
Battery backup time | 15min - 240min, configure according to actual needs | |
Mains power feed-out ways | 4/9/12 ways IT + air conditioner + fire-fighting systems + lighting + communication | |
UPS feed-out ways | 4/9/12 ways IT | |
AC lightning protection | Class C | |
PDU | Ordinary/Intelligent: support IEC or national standard socket | |
Monitoring system | Monitoring system host | Support Web direct access and centralized monitoring of multiple sites |
Local interface | 10.1-inch industrial touch screen | |
Standard configuration | Water leak detector, smoke detector, temperature and humidity sensor, cabinet light strip, door sensor, SMS alarm/router, power supply and distribution / UPS / air conditioner monitoring | |
Optional configuration | Automatic spring door device, fresh air module, camera/audible and visual alarm/infrared, firefighting module, mobile APP | |
Protocol format | Modbus TCP/IP | |
Firefighting system | Installation | Rack-mounted installation |
Starting mode | Smoke and temperature sensor dual interlock pre-action system | |
Gas type | Heptafluoropropane |